Case Studies
Enterprises Data Center

Enterprise DC (Brownfield DC) – Facility summary
- Total DC Area- 2900 sq. ft.
- Designed rack capacity : 6kW
- Number of racks : 46
- Supply grills used – 46 No’s
- Return air grills used- 41 numbers
- 20TR-3 No’s of PAHU (All are operational without standby)-210kW cooling capacity
- Ceiling return air path used for recycling of air

Facility DC Summery: Proposed Design Parameters for new Data center
- Approx. DC area is 4400Sq. ft. (Including PAC room)
- Current IT load planned – 170kW
- Space cooling load : 65kW, (Total cooling load: 235kW)
- UPS : 1x450kVA and 1x350kVA
- Future expected expansion – 100kW additional (Total IT load : 270kW)
- Number of racks – 110 (20no’s – 3phase & 90no’s – 1phase racks)
- Ceiling return distribution system used for recirculation air
- Bottom through CRAC in use
- Designed with 8 No’s of 22TR CRAC units : DX Type
- 6 CRAC units operational with 2 standby

Facility DC Summery:
- This is brownfield data center, with sq ft area : 8352
- Current IT load planned – 790kW
- Per rack load varies from 3kW to 6kW
- Space cooling load : 116kW
- Total cooling load : 906kW
- Installed cooling capacity : 22no’sx30TR
- Number of racks – 252
- Ceiling return distribution system used for recirculation air
- Bottom through CRAC in use

Facility DC Summery: Brownfield Data center
- Data center area Sq. ft. : 2347
- Total no’s of racks : 60
- Installing UPS capacity : 3x500kVA
- Data center UPS load (IT load) – Presently : 202
- Installed cooling capacity : 185/660
- PAHU units 43TRx2 No’s : 86/301
- DX units 33TRx3 No’s : 99/346
- No’s of supply grills : 52
- No’s of Return air grills : 54
- Air distribution system : Ceiling & Room return